64/110kV XLPE Insulated, PE Sheathed High Voltage Power Cables
Nominal Voltage:
64/110KV
Standard:
IEC 60840
Category:
High Voltage Cable
E-mail:
Description
64/110kV XLPE Insulated, PE Sheathed High Voltage Power Cables
APPLICATIONS
These single core cables are designed for distribution of electrical power with nominal voltage 64/110kV. They are suitable These single core cables are designed for distribution of electrical power with nominal voltage 64/110kV. They are suitable
Standard IEC 60840
CONSTRUCTIONV
Conductor: The cable conductors can be made of copper or aluminium, depending on customer’s preference or current carrying capacity. Large size solid conductors are made of aluminium. Available constructions including: round solid conductors up to 2000mm² (RE); circular stranded compacted conductors up to 1200mm² (RM); circular conductors with shaped wires up to 2000mm² (RM, Keystone conductors); segmental conductors up to 2500 mm² (RMS, Milliken conductors); oval shaped stranded compacted conductors up to 800mm² for external gas pressure cables (OM).
Conductor Screen: Extruded layer of semi-conducting cross-linkable compound is applied over the conductor and shall cover the surface completely.
Insulation: Insulation is of cross-linked polyethylene compound XLPE.
Insulaton Screen: Extruded layer of semi-conducting cross-linkable compound is applied over the insulation.
Metallic Layer: The metallic layer may be applied over the core assembly collectively.
The metallic screen shall consist of either copper tapes or a concentric layer of copper wires or a combination of tapes and wires.
Separation Sheath: Aluminum Tape sheath
Outer Sheath: PE
Dimensional Data
Nom. Cross-Section Area |
Nom. Insulation Thickness |
Copper Wire Screen Area |
Approx. Overall Diameter |
Approx. Weight |
|
CU |
AL |
||||
mm² |
mm |
mm² |
mm |
kg/m |
|
240 |
15.0 |
95 |
65.0 |
5.6 |
4.1 |
300 |
15.0 |
95 |
67.0 |
6.3 |
4.5 |
400 |
15.0 |
95 |
71.0 |
7.2 |
5.0 |
500 |
14.0 |
95 |
72.0 |
8.2 |
5.3 |
630 |
14.0 |
95 |
76.0 |
9.7 |
5.9 |
800 |
14.0 |
95 |
80.0 |
11.6 |
6.7 |
1000 |
14.0 |
95 |
86.0 |
14.0 |
7.4 |
1200 |
14.0 |
95 |
92.0 |
16.0 |
8.7 |
1600 |
14.0 |
95 |
98.0 |
19.9 |
10.4 |
2000 |
14.0 |
95 |
106.0 |
24.2 |
12.0 |
2500 |
14.0 |
95 |
114.0 |
30.0 |
14.3 |
Electrical Data
Nom. Cross- Section Area |
D C Resistance @20°C |
A C Resistance @90°C |
Capacitance per core |
Inductance |
Continuous Current Rating for Single Circuit (in air) |
|||||
Cu conductor |
Al conductor |
|||||||||
Cu |
Al |
Cu |
Al |
Trefoil |
Flat |
Trefoil |
Flat |
|||
mm² |
Ω/km |
Ω/km |
Ω/km |
Ω/km |
µF/km |
mH/km |
A |
A |
||
240 |
0.0754 |
0.125 |
0.0973 |
0.161 |
0.141 |
0.442 |
576 |
715 |
449 |
557 |
300 |
0.0601 |
0.100 |
0.0781 |
0.129 |
0.152 |
0.424 |
658 |
820 |
515 |
642 |
400 |
0.0470 |
0.0778 |
0.0618 |
0.101 |
0.165 |
0.407 |
762 |
955 |
601 |
752 |
500 |
0.0366 |
0.0605 |
0.0492 |
0.0791 |
0.188 |
0.392 |
877 |
1108 |
697 |
878 |
630 |
0.0283 |
0.0469 |
0.0393 |
0.0622 |
0.206 |
0.376 |
1012 |
1292 |
807 |
1023 |
800 |
0.0221 |
0.0367 |
0.0326 |
0.0500 |
0.224 |
0.363 |
1149 |
1483 |
931 |
1189 |
1000 |
0.0176 |
0.0291 |
0.0232 |
0.0375 |
0.251 |
0.349 |
1292 |
1688 |
1060 |
1364 |
1200 |
0.0151 |
0.0247 |
0.0201 |
0.0319 |
0.275 |
0.340 |
1542 |
1974 |
1226 |
1558 |
1600 |
0.0113 |
0.0186 |
0.0156 |
0.0240 |
0.304 |
0.328 |
1741 |
2251 |
1432 |
1834 |
2000 |
0.0090 |
0.0149 |
0.0129 |
0.0193 |
0.336 |
0.318 |
1942 |
2536 |
1619 |
2085 |
2500 |
0.0072 |
0.0119 |
0.0109 |
0.0156 |
0.372 |
0.309 |
2149 |
2836 |
1815 |
2353 |
Keyword:
Related Products
Message



Deqing, Huzhou, Zhejiang, China
MESSAGE