  • pt143091237-iec_60502_aerial_bundled_cable_abc_conductor_hdpe_sheath(1)(1).jpg
  • 图片11.png

LV Aerial Bundled Conductor (ABC) Cables


Nominal Voltage:

0.6/1kV

Standard:

IEC 60502

Category:

Aerial Bundled Cable


AERIAL BUNDLED CABLES(ABC)

LV Aerial Bundled Conductor (ABC) Cables

 

Application

Aerial Bundle Cable (ABC cable) is a very innovat ive concept for overhead power distribution as compared to the conventional bare conductor overhead distribution system. It provides higher level of safety and reliability , lower power losses and ultimate system economy by reducing installation, maintenance and operative cost.

Caledonian LV Aerial Bundle Cables are designed to supply 600/1000 volt aerial service for temporary service at construction sites, as a service drop (power pole to service entrance), as a secondary cable (pole t o pole) or st reet lighting. This over-head cable provides reinforced insulation acc. IEC 61140 and fulfill therefore Class II acc. IEC 61140. It is not flame retardant. But this could be if requested change to a flame retardant cable.

Standard

Basic design to BS 7870 / TNB Specification(IEC 60502) / HD 626 S1 / NFC 33-209 / AS/ NZS 3560-1 standards

Construction

Conductor: Aluminium conductor, round stranded compressed (RM).

insulation: XPLE compound, UV-resistant.

Core identification: 1, 2 resp. 3 raised longitudinal ribs on the surface of the cores. The surface of the neutral core should have at least 12 ribs for cross-sections up to 50 mm² and a minimum of 16 ribs for cores above 50 mm². In the case of five core bundles the surface of the protective core should be smooth.

Electrical Properties

Rated Voltage

0.6/1kV

Test Voltage

4 Veff kV

minimum laying Temperature

-20°C

operating Temperature

-40°C~ +90°C

maximum Short-circuit Temperature

250°C

maximum Conductor Temperature

80°C

minimum Bending radius

18×OD

 Construction Parameter

  • BS 7870

Number of Cores xNominal

Cross Section

Overall Diameter

Weight

Maximum Conductor Resistance

Minimum Breaking Load

Current Rating

No.×mm²

mm

Kg/Km

Ω/Km

KN

A

1x16 RM

8,0

74

1,910

2,5

72

1x25 RM

9,0

106

1,200

4,0

107

1x35 RM

10,5

138

0,868

5,5

132

1x50 RM

11,8

182

0,641

8,0

165

1x70 RM

13,0

252

0,443

10,7

205

1x95 RM

15,4

333

0,320

13,7

240

1x120 RM

17,0

408

0,253

18,6

290

1x150 RM

19,0

502

0,206

23,2

334

1x185 RM

21,0

611

0,164

28,7

389

1x240 RM

24,0

801

0,125

37,2

467

2x16 RM

15,6

147

1,910

2,5

72

2x25 RM

18,0

208

1,200

4,0

107

2x35 RM

20,0

277

0,868

5,5

132

2x50 RM

23,5

361

0,641

8,0

165

 

Number of Cores xNominal

Cross Section

Overall Diameter

Weight

Maximum Conductor Resistance

Minimum Breaking Load

Current Rating

No.×mm²

mm

Kg/Km

Ω/Km

KN

A

2x70 RM

25,4

505

0,443

10,7

205

2x95 RM

30,3

666

0,320

13,7

240

2x150 RM

38,0

1004

0,206

23,2

334

4x16 RM

18,8

286

1,910

2,5

72

4x25 RM

21,2

430

1,200

4,0

107

4x35 RM

24,1

553

0,868

5,5

132

4x50 RM

27,8

746

0,641

8,0

165

4x70 RM

31,8

1.009

0,443

10,7

205

4x95 RM

37,8

1.332

0,320

13,7

240

4x120 RM

54,4

1.632

0,253

18,6

290

4x50 + 1x25 RM

319

814

0,641/1,200

8,0/4,0

165/107

4x50 + 1x35 RM

319

845

0,641/0,868

8,5/5,5

165/132

4x70 + 1x25 RM

360

1105

0,443/1,200

10,7/4,0

205/107

4x70 + 2x25 RM

400

1217

0,443/1,200

10,7/4,0

205/107

4x95 + 1x25 RM

418

1438

0,320/1,200

13,7/4,0

240/107

4x95 + 2x25 RM

420

1544

0,320/1,200

13,7/4,0

240/107

4x120 + 1x25 RM

590

2050

0,253/1,200

18,6/4,0

290/107

Other cross-sections can be offered upon request.

TnB Specification(iEC 60502)

Number of Cores xNominal

Cross Section

Overall Diameter

Weight

Maximum Conductor Resistance

Minimum Breaking Load

Current Rating

No.×mm²

mm

Kg/Km

Ω/Km

KN

A

1x16+1x25 RM

15.3

160

1,910

2,5

72

 

Number of Cores xNominal

Cross Section

Overall Diameter

Weight

Maximum Conductor Resistance

Minimum Breaking Load

Current Rating

No.×mm²

mm

Kg/Km

Ω/Km

KN

A

3x16+1x25 RM

19.0

290

1,200

4,0

107

3x25+1x25 RM

23.2

400

0,868

5,5

132

3x35+1x25 RM

25.6

500

0,641

8,0

165

3x50+1x35 RM

30.0

680

0,443

10,7

205

3x70+1x50 RM

34.9

920

0,320

13,7

240

3x95+1x70 RM

40.6

1270

0,253

18,6

290

3x120+1x70 RM

44.1

1510

0,206

23,2

334

3x150+1x95 RM

49.2

1870

0,164

28,7

389

3x185+1x120 RM

54.9

2340

0,125

37,2

467

3x25+1x25+1x16 RM

23.2

470

1,910

2,5

72

3x35+1x25+1x16 RM

25.6

560

1,200

4,0

107

3x50+1x35+1x16 RM

30.0

740

0,868

5,5

132

3x70+1x50+1x16 RM

34.9

980

0,641

8,0

165

3x95+1x70+1x16 RM

40.6

1330

0,443

10,7

205

3x120+1x70+1x16 RM

44.1

1580

0,320

13,7

240

3x150+1x95+1x16 RM

49.2

1940

0,206

23,2

334

3x185+1x120+1x16 RM

54.9

2410

1,910

2,5

72

Other cross-sections can be offered upon request.

 

 

 